Power Generator (200 KVA)




Rating Definitions  - Prime Power (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528.

 

Conformance Standards

  • IS/IEC 60034-1
  • IS 1460
  • ISO 8528
  • ISO 3046
  • ISO 9001
  • IS 13018


Typical Enclosed Genset Dimensions

Genset Model Rating (kVA) Length (mm) Width (mm) Height (mm) Wet Weight" (kg) Standard Fuel tank Capacity (litre)
C180D5P 180 4200 1350 1850 2704 350
C200D5P 200 4200 1350 1850 2704 350
C225D5P 225 4200 1350 1850 2880 350

Generator set Specificatopns

Model C180D5P C200D5P C225D5P
Duty Prime Prime Prime
Power Rating kVA / kWe 180/144 200/160 225/180
no. of phases 3 3 3
output Voltage and Frequency (V and Hz) 415 V, 50 Hz 415 V, 50 Hz 415 V, 50 Hz
Power Factor 0.8 (lagging) 0.8 (lagging) 0.8 (lagging)
Current (A) 250 278 313
RPM 1500 1500 1500
Engine Specification      
Make Curmmins Curmmins Curmmins
Model QSB6.7-G14 QSB6.7-G14 QSB6.7-G14
MoEF Certified Power (hp) 234 256 280
Required Power for rated KVA (hp) 227 248 277
Cooling liquid Cooled (EG compleat 50:50) liquid Cooled (EG compleat 50:50) liquid Cooled (EG compleat 50:50)
Aspiration Turbocharged, charge air cooled Turbocharged, charge air cooled Turbocharged, charge air cooled
No. of cylinders 6, In-line 6, In-line 6, In-line
Bore (mm) x Stroke (mm) 107 x 124 107 x 124 107 x 124
Compression ratio 17.2:1 17.2:1 17.2:1
Displacement (litre) 6.7 6.7 6.7
Fuel High Speed Diesel High Speed Diesel High Speed Diesel
Fuel consumption @ 75% load with radiator and fan* (litre/hr0 31.8 34.6 38.6
Fuel consumption @ 100% load with raditor and Fan* (litre/hr) 41.75 46.2 50
performance class of generator set ISO 8528-5 G2 ISO 8528-5 G2 ISO 8528-5 G2
Starting System 24 V DC Electrical 24 V DC Electrical 24 V DC Electrical
Lube Oil Specification C14+ 15W40 C14+ 15W40 C14+ 15W40
lube oil Sump Capacity , high-Low level (liter) 17.5-15 17.5-15 17.5-15
Total lubrication System Capacity (litre) 19.5 19.5 19.5
Lube Oil Consumption @ full load** (litre/hr) 0.09 0.09 0.09
Total Coolcant Capacity (litre) 32.4 32.4 32.4
Exhaust pipe size (inch) 5 5 5
Total wet weight (Engine + Radiator) **(kg) 639 639 639
Length x xWidth x Height (Engine) (mm) 1057 x 733 x 1139 1057 x 733 x 1139 1057 x 733 x 1139
Mean Piston Speed (m/s) 6.2 6.2 6.2
Combustion air intake @ 100% load (+-5%) (cfm) 446 455 475
Exhaust Temperature (Degree celsius) 538 543 543
Alternator Specification      
Make Starnford (CGT) Starnford (CGT) Starnford (CGT)
Altenator Frame UCI274G UCI274H UCI274K
Enclosure IP23 IP23 IP23
Voltage Regulation (Max) plus minus 1 % plus minus 1 % plus minus 1 %
Class of Insulation H Class H Class H Class
Winding Pitch 2/3 2/3 2/3
Stator Winding Double layer lap Double layer lap Double layer lap
Rotor Dynamically Balanced Dynamically Balanced Dynamically Balanced
Waveform Distortion / Total Harmonic Distortion No load <1.5%, non Distorting Balanced linear Load < 5% No load <1.5%, non Distorting Balanced linear Load < 5% No load <1.5%, non Distorting Balanced linear Load < 5%
Maximum Unbalanced Load across phases* Less Than or equal to 25% Less Than or equal to 25% Less Than or equal to 25%
Telephonic harmonic Factor <2% <2% <2%

*Fuel consumption data is based on diesel having specific of 0.85 and conforming to IS:1460. Fuel Consumption tolerance IS + 5%

**Oil Consumption data is based on oil having specific gravity of 0.89 and meeting C14 + API categories

*With the condition that None of the phases exceeds its rated current 


Graph

Graph

Looking for Product Name ?