Power Generator (160 KVA)




 

Rating Definitions  - Prime Power (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528.

 

Conformance Standards

  • IS/IEC 60034-1
  • IS 1460
  • ISO 8528
  • ISO 3046
  • ISO 9001
  • IS 13018


Typical Enclosed Genset Dimensions

Genset Model Rating (kVA) Length (mm) Width (mm) Height (mm) Wet Weight" (kg) Standard Fuel tank Capacity (litre)
C140D5P 140 4000 1150 1850 2565 290
C160D5P 160 4000 1150 1850 2603 290

Generator set Specificatopns

Model C140D5P C160D5P
Duty Prime Prime
Power Rating kVA / kWe 140/112 160/128
no. of phases 3 3
output Voltage and Frequency (V and Hz) 415 V, 50 Hz 415 V, 50 Hz
Power Factor 0.8 (lagging) 0.8 (lagging)
Current (A) 195 2230
RPM 1500 1500
Engine Specification    
Make Curmmins Curmmins
Model QSB5.9-G1 QSB5.9-G2
MoEF Certified Power (hp) 184 206
Required Power for rated KVA (hp) 175 197
Cooling liquid Cooled (EG compleat 50:50) liquid Cooled (EG compleat 50:50)
Aspiration Turbocharged, charge air cooled Turbocharged, charge air cooled
No. of cylinders 6, In-line 6, In-line
Bore (mm) x Stroke (mm) 102 x 102 102 x 102
Compression ratio 16.5:1 16.5:1
Displacement (litre) 5.88 5.88
Fuel High Speed Diesel High Speed Diesel
Fuel consumption @ 75% load with radiator and fan* (litre/hr0 24.85 28.41
Fuel consumption @ 100% load with raditor and Fan* (litre/hr) 33 36.9
performance class of generator set ISO 8528-5 G2 ISO 8528-5 G2
Starting System 24 V DC Electrical 24 V DC Electrical
Lube Oil Specification C14+ 15W40 C14+ 15W40
lube oil Sump Capacity , high-Low level (liter) 14.2-12.3 14.2-12.3
Total lubrication System Capacity (litre) 15.7 15.7
Lube Oil Consumption @ full load** (litre/hr) 0.22 0.24
Total Coolcant Capacity (litre) 25.6 25.6
Exhaust pipe size (inch) 4 4
Total wet weight (Engine + Radiator) **(kg) 552 552
Length x xWidth x Height (Engine) (mm) 1066 x 642 x 1029 1066 x 642 x 1029
Mean Piston Speed (m/s) 6 6
Combustion air intake @ 100% load (+-5%) (cfm) 382 400
Exhaust Temperature (Degree celsius) 496 522
Alternator Specification    
Make Starnford (CGT) Starnford (CGT)
Altenator Frame UCI274E UCI274F
Enclosure IP23 IP23
Voltage Regulation (Max) plus minus 1 % plus minus 1 %
Class of Insulation H Class H Class
Winding Pitch 2 / 3 Pinch 2 / 3 Pinch
Stator Winding Double layer lap Double layer lap
Rotor Dynamically Balanced Dynamically Balanced
Waveform Distortion / Total Harmonic Distortion No load <1.5%, non Distorting Balanced linear Load < 5% No load <1.5%, non Distorting Balanced linear Load < 5%
Maximum Unbalanced Load across phases* Less Than or equal to 25% Less Than or equal to 25%
Telephonic harmonic Factor <2% <2%

*Fuel consumption data is based on diesel having specific of 0.85 and conforming to IS:1460. Fuel Consumption tolerance IS + 5%

**Oil Consumption data is based on oil having specific gravity of 0.89 and meeting C14 + API categories

*With the condition that None of the phases exceeds its rated current 

 


Graph

Graph