Power Generator (125 KVA)




 

Rating Definitions  - Prime Power (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. Prime Power (PRP) is in accordance with ISO 8528.

 

Conformance Standards

  • IS/IEC 60034-1
  • IS 1460
  • ISO 8528
  • ISO 3046
  • ISO 9001
  • IS 13018


Typical Enclosed Genset Dimensions

Genset Model Rating (kVA) Length (mm) Width (mm) Height (mm) Wet Weight" (kg) Standard Fuel tank Capacity (litre)
C100D5P 100 4000 1150 1850 2200 290
C125D5P 125 4000 1150 1850 2200 290

Generator set Specificatopns

Model C100D5 C125D5P
Duty Prime Prime
Power Rating kVA / kWe 100/80 125/100
no. of phases 3 Phase 3
output Voltage and Frequency (V and Hz) 415 V, 50 Hz 415 V, 50 Hz
Power Factor 0.8 (lagging) 0.8 (lagging)
Current (A) 139 278
RPM 1500 1500
Engine Specification
Make Curmmins* Curmmins*
Model 6BTAA5.9-G13 6BTAA5.9-G13
MoEF Certified Power (hp) 159 159
Required Power for rated KVA (hp) 129 158
Cooling liquid Cooled (EG compleat 50:50) liquid Cooled (EG compleat 50:50)
Aspiration Turbocharged, charge air cooled Turbocharged, charge air cooled
No. of cylinders 6, In-line 6, In-line
Bore (mm) x Stroke (mm) 102x102 102x102
Compression ratio 16.5:1 16.5:1
Displacement (litre) 5.9 5.9
Fuel High Speed Diesel High Speed Diesel
Fuel consumption @ 75% load with radiator and fan* (litre/hr0 18.32 22.5
Fuel consumption @ 100% load with raditor and Fan* (litre/hr) 24.6 30.25
performance class of generator set ISO 8528-5 G2 ISO 8528-5 G2
Starting System 12 V DC Electrical 12 V DC Electrical
Lube Oil Specification C14+ 15W40 C14+ 15W40
lube oil Sump Capacity , high-Low level (liter) 19.9-14.9 19.9-14.9
Total lubrication System Capacity (litre) 21.4 21.4
Total Coolcant Capacity (litre) 26 26
Exhaust pipe size (inch) 4 4
Total wet weight (Engine + Radiator) **(kg) 523 523
Length x xWidth x Height (Engine) (mm) 1066 x 725 x 1033 1066 x 725 x 1033
Mean Piston Speed (m/s) 6 6
Combustion air intake @ 100% load (+-5%) (cfm) 311 311
Exhaust Temperature (Degree celsius) 553 553
Alternator Specification
Make Starnford (CGT) Starnford (CGT)
Altenator Frame UCI274C UCI274V
Enclosure IP23 IP23
Voltage Regulation (Max) plus minus 1 % plus minus 1 %
Class of Insulation H Class H Class
Winding Pitch 43499 43499
Stator Winding Double layer lap Double layer lap
Rotor Dynamically Balanced Dynamically Balanced
Waveform Distortion / Total Harmonic Distortion No load <1.5%, non Distorting Balanced linear Load < 5% No load <1.5%, non Distorting Balanced linear Load < 5%
Maximum Unbalanced Load across phases* Less Than or equal to 25% Less Than or equal to 25%
Telephonic harmonic Factor <2% <2%

*Fuel consumption data is based on diesel having specific of 0.85 and conforming to IS:1460. Fuel Consumption tolerance IS + 5%

#With the condition that None of the phases exceeds its rated current


Graph

Graph

Looking for Product Name ?